Hit Enter to Search
GSC60 - One instrument for all electrical safety tests and Power Quality analysis

GSC60 - One instrument for all electrical safety tests and Power Quality analysis

CODMETEL: HV000060

Inquire now
  • GSC60 was designed with the aim of making safety of electrical installations visible and valuable, easily and quickly.

  • Thanks to the new HTOS™ system the unit displays a message OK - NOT OK after completing the test. The user interface, totally updated under HTOS™, permits to set and carry out measurements in few steps.

  • You can store all recorded data and create folders and subfolders for each kind of test adding comments and notes by means of virtual keyboard.

  • GSC60 is also a three-phase power and energy consumption analyzer boasting, as unique feature, its FREE APP HTAnalysis compatible with iOS and Android.

  • Test results can be transferred through Wi-Fi onto smartphone or tablet enclosing a picture, a video or a voice note to each measurement.

  • You can transfer everything onto HT Cloud and make data available in real time for your colleagues all over the world.


GSC60 makes the job of installer, electrician or consultant easy, rapid and cost-effective.

HTOS™Control the Power. Get access through touchscreen to your measurement. Quickly set measurement parameters and press GO. Here it is, HTOS™, designed to make your work easier. Its’ result options OK and NOT OK as well as its Help OnLine will make it your best partner and save you time.

Evolution of saving. Virtual keyboard to enter comments Saving on file structure New detailed reports with TopView software

Electrical safety measurements AUTO Function to work easier. Rapid setting of limit values and test voltages through virtual keyboard Setting of Timer for the test where is available.

Earth Resistance Earth resistance with 2- or 3-pole volt-ampere method in TT, TN and IT systems. Soil resistivity with 4-pole Wenner method. Stackless earth ground resistance measurement with T2100 Non-trip earth loop impedance measurement

Power Quality and energy analysis 9 types of electrical systems available. 632 parameters can be recorded for over two months. Real-time display of all waveforms, harmonics, vector diagrams as well as summary function on phases for a quick reading of the most important parameters. Detection of voltage anomalies with a resolution of 20ms. Measures and record the electrical absorption of all the equipment connected to the main power supply.

Functions
Touchscreen colour display  
Integrated WiFi connection and compatibility with HTANALYSIS App  
Continuity of protective circuit with 200mA  
Insulation with voltage 50, 100, 250, 500, 1000VDC  
Time/Current tripping of A, AC General, Selective and Delayed RCDs up to 1000mA  
Time/Current tripping of type B RCDs up to 300mA  
Tripping time and current of RCDs with separate clamp jaws type B, A, AC Standard, Selective and Delayed up to 10A  
Loop impedance P-N, P-P, P-PE and calculation of prospective short-circuit current  
Line/Loop impedance with high resolution (with optional accessory IMP57)  
Percentage voltage drop on the line  
Measurement and recording of leakage currents and environment parameters  
Three-phase Power quality and Energy consumption analysis:  
9 types of electrical systems 1Φ-2wires, 1Φ-split phase, 3Φ-3 wires, 3Φ-Aron, 3Φ-Open Δ, 3Φ-Open Y, 3Φ-2 el. 1/2, 3Φ-4 wires Y, 3Φ-High Leg.
632 parameters can be recorded for over two months  
Voltage Anomalies (dips and peaks) with a resolution of 20ms @50Hz
Measurement/recording of Active, Reactive, Apparent Power  
Measurement/recording of Active, Reactive, Apparent Energy  
Measurement/recording of Cosphi, Power Factor  
Measurement/Recording of Voltage and Current Harmonics up to 49th with THD%  
Voltage/current vector diagram  
Voltage/current waveforms  
Tables or histograms of Harmonics and THD%  
Summary table of main electric parameters  
Help on line on the display  
Protection category CAT IV

Full Batteries at All Times. GSC60 is so compact that a new power technology had to be designed to charge batteries. You just need to power the unit and it will charge the batteries. Or you can always start working by simply replacing them with standard AA batteries.

All in real time! Wi-Fi connection allows you to display on your tablet/smartphone/PC in real time: Waveforms Vector Diagrams Harmonics All parameters of each phase

Zoom, Zoom, Zoom! Enlarge, Jump, Analyze. Two finger needed. With HTAnalysis™ you can: Analyze the full recording on your device Compare up to 16 quantities at the same time Immediately analyze events like voltage dips and peaks Use the JUMP function to know the energy consumption anytime Use again the JUMP function to display to display the harmonicsin any point of the recording

HTAnalysis™ and the electrical safety During the measures campaigns you can: Add text and vocal comments Add to each measure photos and videos Customize your measurements

HT Cloud™ Share. Whenever, whatever and wherever. Install App HTanalysis to avail yourself of HTCloud™ database and share measurement results and recordings with your colleagues anytime and from any place on the planet.

Guidelines
EMC: IEC/EN61326
 EN50160
 EN50522
 EN60909-0
 EN61936-1
 IEC/EN61010-031
 IEC/EN61010-1
 IEC/EN61010-2-032
 IEC/EN61187
 IEC/EN61557-1
 IEC/EN61557-10
 IEC/EN61557-2
 IEC/EN61557-3
 IEC/EN61557-4
 IEC/EN61557-5
 IEC/EN61557-6
 IEC/EN61557-7
 UNE20460